+86 13012999975

The 200-600kVA series of three-phase input and three-phase output UPS is a new generation of online double-conversion three-phase input and three-phase output UPS. It adopts a modular structure design, fully digital control and three-level technology, and has the advantages of high efficiency, high power density and excellent output quality. It can eliminate various power grid problems and provide customers with stable and reliable power protection.
IDC (Internet Data Center) rooms, large and medium-sized data centers, financial centers, large enterprise data centers, etc.
Power range: 200-600kVA
Operating mode: Three inputs and three outputs
138-485Vac ultra-wide input voltage range and ultra-wide input frequency range, adaptable to harsh power grid environments.
LBS synchronization function enables synchronization of two UPS units, improving system reliability.
Adopts a three-level topology, achieving an overall efficiency of up to 95.5%<sup>6</sup>.
Input power factor up to 0.99, input harmonic current less than 396.
Superior load capacity, capable of handling 100% unbalanced loads, strong load adaptability, and compatible with generators.
Supports 6 units in parallel and sharing a battery pack, with 30-50 battery cells selectable.
Supports no-load aging testing.
7-inch color touchscreen with graphical display, easy to operate.
Intelligent management functions, supporting RS485, SNMP, dry contact, and CAN interfaces.
| Category | Parameter | 33200 (200kVA) | 33300 (300kVA) | 33400 (400kVA) | 33500 (500kVA) | 33600 (600kVA) |
|---|---|---|---|---|---|---|
| Capacity | ||||||
| Capacity | Rated Capacity (kVA) | 200 | 300 | 400 | 500 | 600 |
| Input | ||||||
| Input | Wiring System | 3-Phase 5-Wire | ||||
| Rated Input Voltage (Vac) | 380/400/415 | |||||
| Input Voltage Range (Vac) | 138~485 | |||||
| Input Frequency Range (Hz) | 40Hz-70 | |||||
| Input Power Factor | >0.99 | |||||
| Input Current THDi | ≤3% (100% linear load) | |||||
| Bypass Voltage Range | 220Vac upper: 25% (+10%,+15%,+20% opt); 230Vac upper: 20% (+10%,+15% opt); 240Vac upper: 15% (+10% opt); Lower: -45% (-10%,-20%,-30% opt) | |||||
| Generator Connection | Supported | |||||
| Output | ||||||
| Output | Wiring System | 3-Phase 5-Wire | ||||
| Rated Output Voltage (Vac) | 380/400/415 | |||||
| Output Power Factor | 0.9 | |||||
| Voltage Accuracy | ±1% | |||||
| Frequency (Mains Mode) | ±1%/±2%/±4%/±5%/±10% adjustable | |||||
| Frequency (Battery Mode) | (50/60 ±0.1%)Hz | |||||
| Current Crest Ratio | 3:1 | |||||
| Output Voltage THDv | ≤2% (100% linear load); ≤4% (100% non-linear load) | |||||
| Overall Efficiency | 95.5% | |||||
| Overload Capacity | 110% load: 60min → bypass; 125% load: 10min → bypass; 150% load: 1min → bypass | |||||
| Battery | ||||||
| Battery | Battery Voltage | ±180/192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30-50 cells optional) | ||||
| Functions | ||||||
| Functions | Transfer Time | Mains to bypass: 0ms (tracking); Mains to battery: 0ms | ||||
| Alarm Functions | Overload, mains abnormality, UPS fault, battery undervoltage, etc. | |||||
| Protection Functions | Battery undervoltage, output over/under voltage, short circuit, overload, over temperature, fan fault alarm, surge protection | |||||
| Communication Interfaces | CAN, RS485, FE, LBS, parallel card, SNMP adapter (opt), relay card (opt) | |||||
| Environment | ||||||
| Environment | Operating Temperature | 0°C ~ 40°C | ||||
| Storage Temperature | -25°C ~ 55°C | |||||
| Humidity Range | 0~95% (non-condensing) | |||||
| Operating Altitude (m) | <1500 | |||||
| Noise (dB at 1m) | <65 | <68 | <70 | <70 | <70 | |
| Physical | ||||||
| Physical | Dimensions (D×W×H mm) | 850×600×2000 | 850×1200×2000 | |||
| Net Weight (kg) | 335 | 400 | 638 | 740 | 843 | |
| Standard | ||||||
| Standard | Applicable Standard | YD/T 1095-2018 | ||||